4.3.2.3 Display Devices

Figure 4.29 Display Devices of BD630 (Safety IO Board)

Table 4-9 Description of the Display Devices of the BD630 (Safety IO Module)

Name

Contents of display

Color

When normal

Actions to take when an abnormality occurs

SEG1

Status information

Red

Will display the defined numbers and characters

Symptom: Undefined numbers or characters are displayed, or the lamp is turned off

Action: Replace the BD630 board.

SEG2

Status information

Red

Will display the defined numbers and characters

Symptom: Undefined numbers or characters are displayed, or the lamp is turned off

Action: Replace the BD630 board.

LEDG3

Magnet Contact (MC) status (Chain 1)

Green

1. Lamp on when closed

2. Lamp off when opened

Symptom: Malfunction

Action: Replace the BD630 board.

LEDG4

Magnet Contact (MC) status (Chain 2)

Green

1. Lamp on when closed

2. Lamp off when opened

Symptom: Malfunction

Action: Replace the BD630 board.

LEDG5

Setting for the Operational Panel (OP) installation (Chain 1)

Green

1. Lamp on when setting for installation

2. Lamp off when setting for non-installation

Symptom: Malfunction

Action: Replace the BD630 board.

LEDG6

Setting for the Operational Panel (OP) installation (Chain 2)

Green

1. Lamp on when setting for installation 2. Lamp off when setting for non-installation

Symptom: Malfunction

Action: Replace the BD630 board.

LED8

External IO 24V power (Chain 2)

Green

Lamp on

Symptom: The lamp is turned on in red or turned off.

Action 1: Check the SMPS 24V power (including the fuse).

Action 2: Check the short-circuiting of the external IO (connectors).

LED10

External IO 24V power (Chain 1)

Green

Lamp on

Symptom: The lamp is turned on in red or turned off.

Action 1: Check the SMPS 24V power (including the fuse).

Action 2: Check the short-circuiting of the external IO (connectors).

LED13

24V power (Chain 1)

Green

Lamp on

Symptom: The lamp is turned on in red or turned off.

Action 1: Check the SMPS 24V power (including the fuse).

Action 2: Replace the BD630 board.

LED14

24V power (Chain 2)

Green

Lamp on

Symptom: The lamp is turned on in red or turned off.

Action 1: Check the SMPS 24V power (including the fuse).

Action 2: Replace the BD630 board.

LEDR22

BD640 error

Red

Lamp off

Symptom: The lamp is turned on in red.

Action 1: Replace the BD640 board.

Action 2: Replace the BD630 board.

LEDR23

H6COM error

Red

Lamp off

Symptom: The lamp is turned on in red.

Action 1: Replace H6COM.

Action 2: Replace the BD630 board.

LEDG01

PLC power (DC24V)

Green

Lamp on

Symptom: The lamp is turned off.

Action 1: Check the PLC24V power (including the fuse).

Action 2: Replace the BD630 board.

LEDG1

CAN LED

Green

Lamp on

Symptom: The lamp is turned off.

Action 1: Replace the CAN cable.

Action 2: Replace the BD631 board.

Action 3: Replace the BD630 board.

Figure 4.30 Placement of the Display Devices of the BD631 (Safety EC Board)

Table 4-10 Description of the Display Devices of the BD631 (Safety EC Module)

Name

Contents of display

Color

When normal

Actions to take when an abnormality occurs

LEDG01

24V power

Green

Lamp on

Symptom: The lamp is turned off.

Action 1: Check the SMPS 24V power (including the fuse).

Action 2: Replace the BD610 board.

LEDG26

CAN LED

Green

Lamp on

Symptom: The lamp is turned off.

Action 1: Replace the CAN cable.

Action 2: Replace the BD631 board.

Action 3: Replace the BD630 board.

LEDG21

LEDG22

LEDG23

LEDR21

LEDG24

EtherCAT LED

Green

Lamp on

Symptom: The LEDR21 lamp is turned on (red).

Action 1: Replace the EtherCAT cable.

Action 2: Replace the BD631 board.