4.3.5.2 Connectors of BD6C2

The placement of the connectors of the electronic board (BD6C2) is shown in the following figure, and the usage and connection devices for each are as shown in Table 4-39.

Figure 4.48 Connectors of the Electronic Board (BD6C2)

Table 4-42 Types and Usage of the Connectors of BD6C2

Name

Usage

Specification

CNAC

3-phase power input for control

3-phase 220V

CN220

CMSMPS power output

Single-phase 220V

CNFN1-4

AC fan power output

Single-phase 220V

CNPR1

Inrush current limiting circuit input

3-phase 220V, MC1 input side

CNPR2

Inrush current limiting circuit output

3-phase 220V, MC2 output side

CNBKAC

Brake SMPS input

Single-phase 220V

CNBKDC

Brake SMPS output

24VDC

CNPB1

Brake control power

24VDC, PB, BD640

CNPB2

Brake control power

24VDC, PB, Reserved

CNPRC

Inrush current limiting circuit control and monitoring

BD640 CNPRC

CNFPS1

CMSMPS power failure detection signal output 1

H6COM DIO

CNFPS2

CMSMPS power failure detection signal output 2

Reserved

CNMC1

Electronic contact MC1 control and monitoring

MC1

CNMC2

Electronic contact MC2 control and monitoring

MC2

CNMC

Electronic contact control and monitoring

BD630 CNMC

CN24VB

Control power input for each module

24VDC, CMBUFFER output

CN24VB1-8

Control power output for each module

24VDC, CN24VB for each module

CNBM

CMSMPS power failure detection signal input

CMSMPS 13–14