4.3.2.3 Display Devices
Last updated
Last updated
Table 4-9 Description of the Display Devices of the BD630 (Safety IO Module)
Name
Contents of display
Color
When normal
Actions to take when an abnormality occurs
SEG1
Status information
Red
Will display the defined numbers and characters
Symptom: Undefined numbers or characters are displayed, or the lamp is turned off
Action: Replace the BD630 board.
SEG2
Status information
Red
Will display the defined numbers and characters
Symptom: Undefined numbers or characters are displayed, or the lamp is turned off
Action: Replace the BD630 board.
LEDG3
Magnet Contact (MC) status (Chain 1)
Green
1. Lamp on when closed
2. Lamp off when opened
Symptom: Malfunction
Action: Replace the BD630 board.
LEDG4
Magnet Contact (MC) status (Chain 2)
Green
1. Lamp on when closed
2. Lamp off when opened
Symptom: Malfunction
Action: Replace the BD630 board.
LEDG5
Setting for the Operational Panel (OP) installation (Chain 1)
Green
1. Lamp on when setting for installation
2. Lamp off when setting for non-installation
Symptom: Malfunction
Action: Replace the BD630 board.
LEDG6
Setting for the Operational Panel (OP) installation (Chain 2)
Green
1. Lamp on when setting for installation 2. Lamp off when setting for non-installation
Symptom: Malfunction
Action: Replace the BD630 board.
LED8
External IO 24V power (Chain 2)
Green
Lamp on
Symptom: The lamp is turned on in red or turned off.
Action 1: Check the SMPS 24V power (including the fuse).
Action 2: Check the short-circuiting of the external IO (connectors).
LED10
External IO 24V power (Chain 1)
Green
Lamp on
Symptom: The lamp is turned on in red or turned off.
Action 1: Check the SMPS 24V power (including the fuse).
Action 2: Check the short-circuiting of the external IO (connectors).
LED13
24V power (Chain 1)
Green
Lamp on
Symptom: The lamp is turned on in red or turned off.
Action 1: Check the SMPS 24V power (including the fuse).
Action 2: Replace the BD630 board.
LED14
24V power (Chain 2)
Green
Lamp on
Symptom: The lamp is turned on in red or turned off.
Action 1: Check the SMPS 24V power (including the fuse).
Action 2: Replace the BD630 board.
LEDR22
BD640 error
Red
Lamp off
Symptom: The lamp is turned on in red.
Action 1: Replace the BD640 board.
Action 2: Replace the BD630 board.
LEDR23
H6COM error
Red
Lamp off
Symptom: The lamp is turned on in red.
Action 1: Replace H6COM.
Action 2: Replace the BD630 board.
LEDG01
PLC power (DC24V)
Green
Lamp on
Symptom: The lamp is turned off.
Action 1: Check the PLC24V power (including the fuse).
Action 2: Replace the BD630 board.
LEDG1
CAN LED
Green
Lamp on
Symptom: The lamp is turned off.
Action 1: Replace the CAN cable.
Action 2: Replace the BD631 board.
Action 3: Replace the BD630 board.
Table 4-10 Description of the Display Devices of the BD631 (Safety EC Module)
Name
Contents of display
Color
When normal
Actions to take when an abnormality occurs
LEDG01
24V power
Green
Lamp on
Symptom: The lamp is turned off.
Action 1: Check the SMPS 24V power (including the fuse).
Action 2: Replace the BD610 board.
LEDG26
CAN LED
Green
Lamp on
Symptom: The lamp is turned off.
Action 1: Replace the CAN cable.
Action 2: Replace the BD631 board.
Action 3: Replace the BD630 board.
LEDG21
LEDG22
LEDG23
LEDR21
LEDG24
EtherCAT LED
Green
Lamp on
Symptom: The LEDR21 lamp is turned on (red).
Action 1: Replace the EtherCAT cable.
Action 2: Replace the BD631 board.